Details
Applications
For clean liquids, without abrasives, which are non-aggressive for the pump materials (contents of solids up to 0.2%).
For heating, conditioning, cooling and circulation plants.
For civil and industrial applications.
When low noise operation is required.
Motor
2-4-pole induction motor, 50 Hz.
Three adjustable speeds.
NC: three-phase 230V or 400 V.
NCM: single-phase 230 V.
Insulation class F.
Protection IP 43.
Operating conditions
Liquid temperature from -10 °C to +120 °C (in short-time duty up to + 140 °C).
Ambient temperature up to 40 °C.
Maximum glycol quantity: 50% (Mixture with more than 20% glycol content require rechecking of the pumping data).
Maximum permissible working pressure 6/10 bar.
