Lowara 15SV11F110T/D Multistage Pump

Quick Overview

  • Type: 15SV11F110T/D
  • Family code: 3N
  • Part number:  1016LD501
  • Voltage: 3 x 400/690V
  • Power: 11kW
  • Weight: 109kg
  • 15 - Flow rate in m3/h
  • SV - series name
  • 11 - number of impellers
  • F - AISI 304, round flanges (PN 25)
  • 110 - Rated motor power (kW x 10)
  • T - Three phase
  • D - Letter assigned by manufacturer
Check the datasheets in the downloads tab below for comprehensive information before you order
Please ensure you are ordering the correct pump/phase as restocking charges may apply. Please call us on 01322 292 415 to check current delivery times.
Excl. Tax: £3,146.00 Incl. Tax: £3,775.20
View Detail
OR

Details

The 15SV11F110T/D electric vertical multistage pump from Lowara is suited for civil, agricultural, light industry, water treatment, and heating and air conditioning market sectors. 

 

Applications 

  • Handling of water, free of suspended solids, in the civil, industrial and agricultural sectors.
  • Pressure boosting and water supply systems.
  • Irrigation systems.
  • Wash systems.
  • Water treatment plants.
  • Handling of moderately aggressive liquids, demineralised water, water and glycol, etc.
  • Circulation of hot and cold water for heating, cooling and conditioning systems.
  • Boiler feed.
  • Pharmaceutical food & beverage industries.

Pump Specifications

  • The SV pump is a non-self priming vertical multistage pump coupled to a standard motor.
  • The liquid end, located between the upper cover and the pump casing, is held in place by tie rods. The pump casing is available with different configurations and connection types.
  • Delivery: up to 24 m3/h.
  • Head: up to 250 m.
  • Temperature of pumped liquid:
    - from -30°C to +120°C for standard version.
  • Maximum operating pressure:
    - With oval flanges: 16 bar (PN16) at 50°C.
    - With round flanges: 25 bar (PN 25) at 50°C.
  • Hydraulic performance compliant with ISO 9906:2012 - Grade 3B (ex ISO 9906:1999 - Annex A).
  • Direction of rotation: clockwise looking at the pump from the top down (marked with an arrow on the adaptor and on the coupling).

Motor Specifications

  • Squirrel cage in short circuit, enclosed construction with external ventilation.
  • IP55 protection.
  • Class 155 (F) insulation.
  • Performances according to EN 60034-1.
  • Standard voltage:
    - Three-phase version: 400/690V, 50 Hz.